AERIAL BUNCHED CABLE (ABC)

Aerial bundled cables (simply ABC) are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor. This contrasts with the traditional practice of using un-insulated conductors separated by air gaps. This variation of overhead power lines utilizes the same principles as bundled conductors, except that they are closer together to the point of touching but each conductor is surrounded by an insulating layer (except for the neutral line).

CONSTRUCTION

1-CONDUCTOR

A-Phase or Streetlight Conductor

The phase conductor and neutral/street lighting conductors is of H2 or H4 grade aluminium complying with the requirements of IS 8130:1984 and conforms to flexibility class 2 of IS 8130:1984. The size of the street lighting conductor is16 mm2

B-Messenger (Neutral Conductor or Otherwise)

The conductor is heat treated aluminium- magnesium-silicon alloy wire conforming to IS 398 (Part 4):1979.It is either stranded circular or compacted circular type and has minimum 7 strands with smooth surface.

2-INSULATION

The conductor is insulated with crosslinked polyethylene applied by extrusion. The insulation so applied fits closely on the conductor and it is possible to remove without damaging the conductor. The color of insulation is black, offering UV protection.

3-CORE IDENTIFICATION

he phase conductors is provided with one, two or three 'ridges' and outer neutral insulated conductor, if provided, has four 'ridges' for quick identification. The street lighting conductor and messenger conductor (if insulated) does not have any identification mark.

4-ASSEMBLY (LAYING UP)

The required number of insulated phase conductors, one insulated neutral conductor (if required) and a street lighting conductor (if required) is twisted around the bare (or insulated) as required messenger conductor without fillers with a lay not exceeding 35times the diameter of the insulated phase conductor. The direction of lay is right hand.

APPLICATION

Aerial Bunched Cables are suitable for the following functions

ADVANTAGES

Aerial Bunched Cables Lines have very high reliability in maintaining services because conductors are insulated with the best dielectric. The benefits of using this line are:

MANUFACTURING CAPABILITY

SR. NO. DESCRIPTION RANGE
1
Cable construction & Area
1CORE X 16 SQMM +1CORE 25 SQMM TO 4CORE X 120+ 1CORE 95 SQMM +1CORE 16 SQMM

PHYSICAL PROPERTIES

SR. NO. DESCRIPTION TEMPTATURE
1
Permissible Temp in continuous operation
90°C
2
Temp in a short circuit (duration up to 5s)
250°C

Note: The Catalogue conductor Parameter are informative and can be customized as per Project Requirements

APPLICABLE STANDARD

Aerial bundled cables (simply ABC) can be supplied to meet various National & International Standards as follows

IS-14255, IS 8130   |  IEC 60502 Part 1   |  NFC 33-209  

Phase Conductor
(Aluminium)
Street Lighting Conductor
(Aluminium)
Messenger Conductor
Aluminium Alloy
As per IS 8130 : 1984
As per IS 8130 : 1984
As per IS 398 (Part-4) 1994
Nom. Area
Max. D.C. Conductor Resistance at 20°C
Nom. Thickness of Insulation XLPE/PE
Nom. Area
Max. D.C. Conductor Resistance at 20°C
Nom. Thickness of Insulation
Nom. Area
Max. D.C. Conductor Resistance at 20°C
Min. Breaking Load
Sqmm
Ω/Km
mm
Sqmm
Ω/Km
mm
Sqmm
Ω/Km
KN
16
1.910
1.2
16
1.91
1.2
25
1.380
7.0
25
1.200
1.2
16
1.91
1.2
25
1.380
7.0
35
0.868
1.2
16
1.91
1.2
25
1.380
7.0
50
0.641
1.5
16
1.91
1.2
35
0.986
9.8
70
0.443
1.5
16
1.91
1.2
50
0.689
14.0
95
0.320
1.5
16
1.91
1.2
70
0.492
19.7
120
0.253
1.5
16
1.91
1.2
95
0.357
26.5